APC Back-UPS RS,600 Watts /1000 VA,Input 120V /Output 120V, Interface Port USB, Rack Height 2.

2 个问题 查看全部

Overload alarm lights and sound

My ups, after 5 years of continuous operation shows the overload's light .

I unplugged the PC and I replaced the battery but I have not solved the problem.

Then I opened it to see if there are components that are burned or leak but nothing.

To be sure I replaced the cooling fan but nothing has changed.

Can anyone give me some tips?

Thank you very much.

已回答! View the answer 我也有这个问题

这是一个好问题吗?

按维修分数 4

评论:

Hi, i had the same problem twice...!!!

My battery was ok, everything was ok but

the beep keep going on, for overload...

Both times i fixed doing these steps...

- Turn off the unit

- Flip over the unit

- Open the battery-cap and turn the power on

- Green Light is flashing

- Try Now (with the green light flashing) to disconnect the battery...

- Now it should be ON with the Empty battery light on (Red light)

- Connect again the battery as it is...

Now it should be ok...!!!

Good Luck...

添加一条评论

Macbook 电池维修套装

起价 $69.99

Buy Now

Macbook 电池维修套装

起价 $69.99

Buy Now

5个回答

已选择的解决方案

Thanks to all. I have not solved the problem. I replaced the old ups with a new one.

这个答案有帮助吗?

按维修分数 1
添加一条评论
最有帮助的答案

Roberto, If it alarms, even with nothing plugged in, then it is possible that one of the MOSFET on your mainboard has failed.

这个答案有帮助吗?

按维修分数 4

评论:

metal–oxide–semiconductor field-effect transistor (MOSFET)

http://en.wikipedia.org/wiki/MOSFET

Did you solve the problem? Same problem here, 4 years later..

daigoph@gmail.com

添加一条评论

Hi, i had the same problem twice...!!!

My battery was ok, everything was ok but

the beep keep going on, for overload...

Both times i fixed doing these steps...

- Turn off the unit

- Flip over the unit

- Open the battery-cap and turn the power on

- Green Light is flashing

- Try Now (with the green light flashing) to disconnect the battery...

- Now it should be ON with the Empty battery light on (Red light)

- Connect again the battery as it is...

Now it should be ok...!!!

Good Luck...

这个答案有帮助吗?

按维修分数 2

评论:

Thank you but I replaced the old ups with a new one. Yours sincerely.

添加一条评论

I too facing the same problem....battery charging process is fine...but when i turn on the inverter it trips and shows overload and keep continuosly beep beeps....pls help me to solve this problem....i expecting board level service suggestions ...thank you

这个答案有帮助吗?

按维修分数 1
添加一条评论

My problem solved with removing the all cables also power cable wait 5 minute & connect cable again it's working.

这个答案有帮助吗?

按维修分数 0
添加一条评论