The APC RS 1000 is an uninterruptible power supply capable of delivering 600 Watts.
kvpselvam @kvpselvam
声誉积分: 1
发帖于: 2016年6月28日
after replacing the battery after long non use all the lights are flashing and and no output
这是一个好问题吗?
1条评论:
kvpselvam all LED's flashing at the same time indicates an internal fault. Time to take it apart and check the circuit boards and capacitors.
由 oldturkey03 完成的 2016年6月28日
ciradrak @ciradrak
声誉积分: 448
11
6
2
发帖于: 2018年11月14日
If the batteries have been replaced the UPS may need to charge them before it will respond correctly. Leave the UPS plugged in but off for 8 hours, then try again; before blaming a circuit board.
这个答案有帮助吗?
过去 24 小时: 0
过去 7 天: 1
过去 30 天: 2
总计 1,400
kvpselvam all LED's flashing at the same time indicates an internal fault. Time to take it apart and check the circuit boards and capacitors.